200m OPGW 36 Core Optical Ground Wire On Power Transmission Lines G652d Fiber

Contact me for free samples and coupons.
Whatsapp:0086 18588475571
Wechat: 0086 18588475571
Skype: sales10@aixton.com
If you have any concern, we provide 24-hour online help.
xFiber Type | G652d | Fiber Count | 36 Core |
---|---|---|---|
Tube | AL Tube | Material | Aluminium,galvanized Steel,Aluminium Alloy/Aluminium Clad Steel |
Application | Overhead,self Support | Surface | Smooth |
Package | Drum With Surdace | Span | 100m/150m/200m/400m |
Item | Overhead Line Fittings | Oem | Provided |
High Light | OPGW 36 core fiber optic cable,G652d 200m fiber optic cable,36core optical ground wire |
Optical Fiber Composite Ground Wire 36 Core Single Mode Uni-Tube Overhead Aerial Opgw Cable
Description:
OPGW is a kind of overhead ground wire containing optical fiber, which has multiple functions such as overhead ground wire and optical communication. It is applicable to new aerial power route to satisfy the needs for big conductors and high voltage transmission, and is used to conduct large fault short circuit current to provide anti lightning protection.
Application:
Optical fiber composite ground wire [OPGW] is suitable for installation on new power lines with double function of ground wire and communication. Especially for installation on normal voitage and extra high voltage power lines. OPGW can replace conventional ground wire of old power line with increasing fiber communication function. They conduct short circuit current and provide lightning resistance.
Product Characteristics:
• Large diameter, large fiber capacity
• The structure is stable and the reliability is high
• Excellent capability against side and outstanding short circuit current capacity
• The optimum stranding design can obtain the surplus length of secondary optical fiber • The number of strands can be designed in two or three layers
• Match with common ground wires
Classification | Material | Value | ||
Construction |
Optical Fibre | G652D/G655 etc. | 2 - 144 | |
Protection Tube | Stainless steel tube | 1.5 - 6mm | ||
Stranded Line | AS wire/AA wire/Al Rod | 1.5 - 6mm | ||
Max. Diameter | 30mm | |||
Max. Cross Section | 500mm2 | |||
Characteristic |
According to the standards as DL/T 832, IEC60794-4-10, IEEE1138 | |||
Max. Tensile Strength (RTS ) (kN) | 700 | |||
Max. Crush Strength(N/100mm) | 3000 | |||
Max. Short Current Capacity (40℃ to 200℃)(kA2s) | 2000 | |||
Min. Bending Radius (Dynamic) | 20D | |||
Min. Bending Radius (Static) | 15D | |||
Environment Performance | Installation (℃) | -10 to +50 | ||
Transportation and Operation (℃) | -40 to +65 |
NO. | Subject | Unit | Technical parameter |
1 | Optic fiber type | / | G.652D |
2 | Numbers of optic fiber cores | Cores | 96/128 |
3 | Attenuation characteristics | 1310nm(dB/km) | ≤0.35 |
1550nm(dB/km) | ≤0.22 | ||
4 | Cable external diameter | mm | ≤12.8 |
5 | Weight per unit length of optic cable | kg/km | ≤502 |
6 | Total cross section | mm² | 79.38 |
Cross section of aluminum clad steel wire | mm² | 79.38 | |
7 | Rate tensile strength RTS | kN | 62.0 |
8 | Elastic modulus | GPa | 132 |
9 | Linear expansion coefficient | ×10-6/℃ | 13.8 |
10 | 20℃ DC resistance | Ω/km | ≤0.740 |
11 | Shortcut current(0.5s,20℃~200℃) | kA | 9.21 |
12 |
Allowable short circuit current capacity (0.5s,20℃~200℃) |
kA².S | ≥42.4 |
13 | Maximum allowable temperature | ℃ | 200 |
14 | Maximum allowable tension(40%RTS) | kN | 24.80 |
15 | Annual average operatingtension(25%RTS) | kN | 15.50 |
16 | Minimum allowable bending radius | operation:mm | 15D |
construction:mm | 20D | ||
17 | Storage installation temperature | Storage(℃) | -40~+80 |
Installation(℃) | -10~+50 |